You can set alarm limits, configure alarm actions
and turn alarms on and off via the setup
dialog.
|
 |
Any user can view the current alarm settings,
but to make changes, you
must first
be logged in as a Supervisor. |
 |
Accessing the Alarms Setup Page
From the home screen or the main run-screen, in monitor-mode or
run-mode, press the setup button, then select the alarms icon.
  This
takes you to the alarms setup page.
From here you can:
- View the Alarm
Panel where you can see which zones are registering an
alarm.
- View the Alarm
Setup Panel where
you can see the current alarm values and limits, and make changes.
- View and change the Alarm
Actions to be taken by the controller in the event of an
alarm condition being detected.
- View the Alarm
Log.
- Change alarm settings and actions for the water-zones, if
fitted.
Types of Alarm The controller is able to
detect the following alarms:
- Open
Thermocouple (manifolds only). The controller cannot read a
zone's temperature.
- Reversed
Thermocouple (manifolds only). The temperature readings from the
zone are incorrect.
- Cold
Thermocouple (manifolds only). The temperature readings from the
zone are incorrectly lower than the actual temperature.
- No-Load.
The zone's heater (or connection to it) is faulty,
- Temperature
Tolerance (manifolds only). The zone's temperature has drifted
beyond a set amount from the setpoint.
- Power
Tolerance (cavities only). The zone's heater is
drawing more (or less) than a set amount of power than the average
power drawn by the cavities.
- Tool
Motion.
Controllers fitted with a machine interface can detect when
the
tool is moving. This alarm can be set to trigger when a
minimum
number of movements is not detected.
Water Zones (if fitted) have their own alarms.
Alarm
Setup
Temperature-Tolerance, Power-Tolerance and Cold-Thermocouple alarms are
controlled by values set by a Supervisor.
The Alarm Setup Panel displays a list of zones, identified by number
and name (if configured).
The current value for each alarm condition is displayed for each zone
in a table.
Here,
zone 7 will trigger the temperature-tolerance alarm whenever it's
temperature strays more than 5 degrees above or below the setpoint.
With
a 12% power-tolerance, the zone will trigger an alarm if it's average
power consumption for it's heater is 12% greater or less than the
average power consumption for all of the cavities. You cannot
set
a power-tolerance for manifolds. The average is taken from
the
last 60 seconds, on a rolling-average basis.
A 15 minute
cold-thermocouple detection time means that the controller expects the
zone to reach setpoint within 15 minutes of starting up.
  Edit Alarms
Changes
to the temperature-tolerance, power-tolerance or cold-thermocouple
alarm limits are made through the Edit Alarm dialog.
This dialog has it's own status-bar, which instructs the user what to
do.
Using the Edit Alarm dialog is easy:
- Select some zones from the list. You can
select zones in any order you wish. The list is populated with the zone
number and the zone name, if one is configured.
- You can use the quick-select buttons on the lefthand
side to quickly select all cavities, all manifolds, or all zones, or
you can cancel your selection.
- Choose the alarm type you want to change for the
selected zones.
- Enter the new value.
- For
temperature-tolerance alarms, the new value is entered in degrees.
This defines a band of temperatures above and below setpoint
which are 'safe' from alarms.
- For power-tolerance alarms, the
new value is entered as a percentage. This defines a range of
values above and below the average power for all cavities which are
'safe' from alarms.
- For cold-thermocouple alarms, the new value defines
the expected warm-up time of the zone(s), in minutes.
To
turn an alarm off, enter zero. The selected zones will not be
checked for the chosen alarm condition if the value displayed is "Off".
Alarm Actions
The controller can take various actions when an alarm condition is
triggered:
- Ignore.
No action is taken.
- Alarm.
The controller toggles the Alarm relay,
which if connected will sound the external machine alarm, start the
alarm indicator lamp and stop the machine. The controller
continues to maintain temperatures and the Alarm
Warning Dialog
is placed on the screen.
- Rest.
All zones are placed into rest mode ,
the Alarm Relay
is toggled and the Alarm
Warning Dialog is placed on the screen.
- Shutdown.
The controller turns all zones off, the Alarm Relay is
toggled and the Alarm
Warning Dialog is placed on the screen.
To make changes to the Alarm Actions page, you must be logged in as a Supervisor.
Spotting
Alarms
This
zone is out of temperature-tolerance (over setpoint), so it's
temperature is coloured red. If a temperature is coloured blue, it is
under setpoint.
Temperatures displayed in green are in-tolerance.
The
zone is also out of power-tolerance (over); it's power level is
coloured red. This zone needs more power than expected in
order
to maintain setpoint. If the zone needed less power than
expected
it would be coloured blue. Zones which are in power-tolerance are
coloured yellow.
These colourings hold true so long as the zone has a configured value
in it's Alarm Setup Panel (i.e.: it is not
set to "off"), even if the Alarm
Action is set to "ignore".
You can select alarms from the list to find out more:
If an alarm action is set to any setting other than "ignore", the Alarm
Warning Dialog
will be displayed and the Alarm
Relay will be toggled. Alarms actions set to
"Alarm" will be removed from the Alarm Warning Dialog when the alarm
condition no longer exists.
When all alarms have been removed from the list, the Alarm
Warning Dialog
will be dismissed automatically, the Alarm relay will be
toggled and the controller will resume normal operation.
However, if an alarm action is set to "Rest" or "Shutdown", the
Alarm Warning Dialog
will remain on-screen. The alarm conditions for these cases are not
removed from the list and the controller will require user intervention
in order to resume normal operation.
All alarm conditions are logged
so you can see which alarms occured and when they were triggered:
You can check whether the Alarm
Relay
has been toggled from the status bar. An orange alarm-bell
icon
is displayed whenever there is an alarm and the alarm relay has been
set to stop the machine from cycling:
|